JLK2-0.66 split core current transformers are designed with a core that can be opened and placed around the conductor, eliminating the need to disconnect the electrical wiring. This feature makes them ideal for retrofit installations where traditional solid-core CTs require disconnecting the conductor.
Series | split core current transformer |
Item Number | JLK2-0.66 |
Rated Primary Current | 100A to 6300A |
Rated Secondary Current | 5A, 1A |
Rated Load | 2.5/5/10/20VA |
Accuracy Class | 1.0, 0.5 |
Rated voltage | AC 0.66kV |
Rated Frequency | 50/60Hz |
Casing Material | PC |
Installation | busbar or floor mounting |
Operating Temperature | -40℃ to +50℃ |
Altitude | ≤ 3000m |
Power Frequency Voltage Endurance | 3000V/1min |
Operating humidity | ≤ 80% |
Function | measurement of current and power; relay protection |
Model | Ratio | Hole Dimensions | Rated Burden | Accuracy Class |
---|---|---|---|---|
JLK2-0.66 30×20 | 100/5A~400/5A | 30x20mm | 2.5~5VA | 3.0, 1.0 |
JLK2-0.66 60×40 | 250/5A~1200/5A | 60x40mm | 2.5~10VA | 1.0, 0.5 |
JLK2-0.66 80×50 | 250/5A~1500/5A | 80x50mm | 5~10VA | 3.0, 1.0, 0.5 |
JLK2-0.66 100×50 | 500/5A~3200/5A | 100x50mm | 5~20VA | 1.0, 0.5 |
JLK2-0.66 120×60 | 500/5A~1500/5A | 120x60mm | 5~10VA | 1.0, 0.5 |
JLK2-0.66 140×60 | 1000/5A~6300/5A | 140x60mm | 10~20VA | 1.0, 0.5 |
JLK2-0.66 160×80 | 1000/5A~6300/5A | 160x80mm | 10~20VA | 1.0, 0.5 |
JLK2-0.66 80×50 | 250/1A~1500/1A | 80x50mm | 5~10VA | 3.0, 1.0, 0.5 |
JLK2-0.66 100×50 | 500/1A~3200/1A | 100x50mm | 5~20VA | 1.0, 0.5 |
JLK2-0.66 120×60 | 500/1A~1500/1A | 120x60mm | 5~10VA | 1.0, 0.5 |
JLK2-0.66 140×60 | 1000/1A~6300/1A | 140x60mm | 10~20VA | 1.0, 0.5 |
JLK2-0.66 160×80 | 1000/1A~6300/1A | 160x80mm | 10~20VA | 1.0, 0.5 |
Window Size: according to the specification and number of busbars.
Rated Current Ratio: 1/3 larger than the measured primary current.
Rated Secondary Current: 5A or 1A. When the installation location of the instrument is far away from the current transformer or the loop load is large, please choose the secondary current of 1A.
Rated Burden: the measuring instrument is connected to terminals S1 and S2, and the total load of the connected circuit should not exceed the transformer’s rated load/burden.
Accuracy Class: for measurement—class 1.0, 0.5, 0.2, 0.5S, 0.2S; for protection—class 5P10, 5P20, 10P10, 10P20.